The High Rate range of VRLA batteries provide reliable battery backup to any High Rate UPS application. All High Rate series batteries use optimized plate technology and a patented post design offering exceptional service life.
Float Charging Voltage
2.25Vpc to 2.27Vpc @ 77° F (25° C)
Equalize Charging Voltage
2.35Vpc to 2.40Vpc @ 77° F (25° C)
See Operations and Maintenance Manual for specific guidelines and recharge times
Maximum AC Ripple (Charger)
0.5% RMS, 1.5% peak-to-peak for float charge voltage for best results
Maximum Charge Current
Electrolyte
Self Discharge Rate
<2% per month at 77°F (25°C)
Relief Valve
Self-resealing; Operates at 2 to 3 psi and is complete with integral flame arrestor
Terminal Type
M8-F
Torque
130 in-lbs (15 Nm)
Operating Temperature Range
Nominal
+74°F (24°C) to 80°F (27°C)
Charge
-20ºF (-28ºC) to +122ºF (50ºC)
Discharge
-40ºF (-40ºC) to +140ºF (60ºC)
Storage Temperature Range
-4ºF (-20ºC) to +104ºF (40ºC)
The Lithium MPLhP and MPLhE Series (LFP) Lithium Iron Phosphate batteries are designed for a wide range of UPS solutions
The HRXL series VRLA batteries are designed to provide Extreme life in conventional temperature applications, as well as longer life than traditional VRLA batteries in high temperature applications.
The High Rate range of VRLA batteries provide reliable battery backup to any High Rate UPS application.