Technical Features:
Compliance and Safety:
Transportation:
Float Charging Voltage
2.25Vpc to 2.27Vpc @ 77° F (25° C)
Equalize Charging Voltage
2.35Vpc to 2.40Vpc @ 77° F (25° C)
See Operations and Maintenance Manual for specific guidelines and recharge times
Maximum AC Ripple (Charger)
0.5% RMS, 1.5% peak-to-peak for float charge voltage for best results
Maximum Charge Current
Electrolyte
Absorbed 1.300 s.g. H2SO4
Self Discharge Rate
<2% per month at 77° F (25° C)
Relief Valve
Self-resealing; Operates at 2 to 3 psi and is complete with integral flame arrestor
Operating Temperature Range
Nominal
+74°F (24°C) to 80°F (27°C)
Charge
-20ºF (-28ºC) to +104ºF (40ºC)
Discharge
-40ºF (-40ºC) to +104ºF (40ºC)
Storage Temperature Range
-4ºF (-20ºC) to +104ºF (40ºC)